SECTION 8 - MICROPANEL
QUANTECH
133
FORM QTC4-NM1
ISSUE DATE: 4/2/2018
8
TABLE 22 - SETPOINT LIMITS
PROGRAM VALUE MODE LOW LIMIT HIGH LIMIT DEFAULT
Leaving Chilled Liquid Setpoint
Water Cooling
40.0°F 60.0°F 44.0°F
4.4°C 15.6°C 6.7°C
Glycol Cooling
15.0°F 70.0°F 44.0°F
-9.4°C 15.6°C 6.7°C
Leaving Chilled Liquid Control Range -
1.5°F 2.5°F 2.0°F
0.8°C 1.4°C 1.1°C
Max. Remote Temperature Reset -
2°F 40°F 20°F
1°C 22°C 11°C
The minimum, maximum, and default values
allowed under the SETPOINTS key are provided in the
following table.