SECTION 5 - TECHNICAL DATA
QUANTECH
61
FORM QTC4-NM1
ISSUE DATE: 4/2/2018
5
UNIT FRAME 300 310 315 320 330 340 340 370 370 UNIT FRAME 370 400 405 410 410 450 490 460 470 480 500
CONDENSER CODE H P P S S S H P S CONDENSER CODE H P S H P S H S C C S
EVAPORATOR CODE C E E E C E E J F EVAPORATOR CODE J J H H J G J G K J J
GENERAL UNIT DATA GENERAL UNIT DATA
Number of Independent
Refrigerant Circuits
2
Number of Independent
Refrigerant Circuits
2
Refrigerant Charge, R-134a,
R-513A, Ckt.-1/Ckt.-2, lbs
(kg)
295/250
(134/114)
315/275
(143/125)
315/295
(143/134)
295/295
(134/134)
290/290
(132/132)
310/310
(141/141)
315/315
(143/143)
475/320
(216/145)
420/245
(191/111)
Refrigerant Charge, R-134a,
R-513A, Ckt.-1/Ckt.-2, lbs (kg)
470/310
(213/141)
475/360
(216/163)
460/345
(209/156)
480/365
(218/166)
475/385
(215/175)
370/370
(168/168)
445/445
(202/202)
385/385
(175/175)
390/390
(179/179)
405/405
(184/184)
445/445
(202/202)
Oil Charge, Ckt.-1/Ckt.-2,
gal (liters)
3.7/3.0
(14.0/ 11.4)
3.9/3.2
(14.8/ 12.1)
3.9/3.3
(14.8/ 12.5)
3.7/3.7
(14.0/ 14.0)
3.7/3.7
(14.0/ 14.0)
3.8/3.8
(14.4/ 14.4)
3.9/3.9
(14.8/ 14.8)
4.1/4.0
(15.5/ 15.1)
4.0/2.9
(15.1/ 11.0)
Oil Charge, Ckt.-1/Ckt.-2, gal
(liters)
4.1/3.8
(15.5/
14.4)
4.1/4.1
(15.5/
15.5)
4.0/4.0
(15.1/
15.1)
4.1/4.1
(15.5/
15.5)
4.1/4.1
(15.5/
15.5)
4.0/4.0
(15.1/
15.1)
4.2/4.2
(15.9/
15.9)
4.0/4.0
(15.1/
15.1)
4.0/4.0
(15.1/
15.1)
4.0/4.0
(15.1/
15.1)
4.2/4.2
(15.9/
15.9)
Minimum Load (%) 10% Minimum Load (%) 10%
Chassis Dimensions -
Length, inches (mm)
423.1
(10748)
423.1
(10748)
467.1
(11865)
379.2
(9631)
423.1
(10748)
423.1
(10748)
467.1
(11865)
511
(12979)
467.1
(11864)
Chassis Dimensions - Length,
inches (mm)
467.1
(11864)
555.3
(14104)
467.1
(11864)
555.3
(14104)
599.3
(15222)
555.3
(14104)
599.3
(15222)
599.3
(15222)
467.1
(11864)
467.1
(11865)
599.3
(15222)
Chassis Dimensions -
Width, inches (mm)
88.3 (2242) 88.3 (2242) 88.3 (2242) 88.3 (2242) 88.3 (2242) 88.3 (2242) 88.3 (2242) 88.3 (2243) 88.3 (2243)
Chassis Dimensions - Width,
inches (mm)
88.3
(2243)
88.3
(2243)
88.3
(2243)
88.3
(2243)
88.3
(2243)
88.3
(2243)
88.3
(2243)
88.4
(2244)
88.3
(2242)
88.3
(2243)
88.3
(2243)
Chassis Dimensions -
Height, inches (mm)
94.6 (2403) 94.6 (2403) 94.6 (2403) 94.6 (2403) 94.6 (2403) 94.6 (2403) 94.6 (2403) 94.7 (2405) 94.7 (2405)
Chassis Dimensions - Height,
inches (mm)
94.7
(2405)
94.7
(2405)
94.7
(2405)
94.7
(2405)
94.7
(2405)
94.7
(2405)
94.7
(2405)
94.7
(2405)
94.6
(2403)
94.7
(2405)
94.7
(2405)
COMPRESSORS, SEMI-HERMETIC SCREW COMPRESSORS, SEMI-HERMETIC SCREW
Qty per Chiller 2 Qty per Chiller 2
CONDENSER FANS CONDENSER FANS
Number Ckt-1/Ckt-2 10/8 10/8 8/8 8/8 9/9 9/9 10/10 14/8 13/7 Number Ckt-1/Ckt-2 13/7 14/10 12/8 14/10 14/12 12/12 13/13 13/13 10/10 10/10 13/13
Air on Condenser
(Min/Max), °F (°C)
0/125
(-17.8/51.7)
Air on Condenser
(Min/Max), °F (°C)
0/125
EVAPORATOR, SHELL AND TUBE HYBRID FALLING FILM
2
EVAPORATOR, SHELL AND TUBE HYBRID FALLING FILM
2
Water Volume, gal (liters) 71 (269) 113 (428) 113 (428) 113 (428) 71 (269) 113 (428) 113 (428) 147 (556) 96 (363) Water Volume, gal (liters) 147(556) 147(556) 130(492) 130(492) 147(556) 96(363) 147(556) 96(363) 130 (492) 147(556) 147(556)
Leaving Water
Temperature (Min/Max), °F
(°C)
2
40/60
(4.4/15.6)
Leaving Water
Temperature (Min/Max), °F
(°C)
2
40/60
(4.4/15.6)
Maximum Water Side
Pressure, psig (barg)
150
(10.3)
Maximum Water Side
Pressure, psig (barg)
150
(10.3)
Maximum Refrigerant Side
Pressure, psig (barg)
235
(16.2)
Maximum Refrigerant Side
Pressure, psig (barg)
235
(16.2)
Evap Drain Connection,
inches (mm)
3/4
Evap Drain Connection,
inches (mm)
3/4
Minimum Chilled Water Flow
Rate, gpm (l/sec)
300
(18.9)
400
(25.2)
400
(25.2)
400
(25.2)
300
(18.9)
400
(25.2)
400
(25.2)
550
(34.1)
460
(29.0)
Minimum Chilled Water Flow
Rate, gpm (l/sec)
550
(34.1)
550
(34.1)
520
(33.0)
520
(33.0)
550
(34.1)
460
(29.0)
550
(34.1)
460
(29.0)
470
(30)
550
(34.1)
550
(34.1)
Maximum Chilled Water Flow
Rate, gpm (l/sec)
1150
(72.6)
1500
(94.7)
1500
(94.7)
1500
(94.7)
1150
(72.6)
1500
(94.7)
1500
(94.7)
1880
(118.1)
1540
(97.0)
Maximum Chilled Water Flow
Rate, gpm (l/sec)
1880
(118.1)
1880
(118.1)
1700
(107.0)
1700
(107.0)
1880
(118.1)
1540
(97.0)
1880
(118.1)
1540
(97.0)
1870
(118)
1880
(118.1)
1880
(118.1)
Inlet and Outlet Water
Connections, in
6
8 8 8
6
8 8 8 8
Inlet and Outlet Water
Connections, in
8 8 8 8 8 8 8 8 8 8 8
TABLE 5 - PHYSICAL DATA - MICROCHANNEL COIL (CONT'D)
NOTES:
1. Shipping and operating weights shown are for base unit; selected options may add weight to unit. Contact your nearest Quantech Sales
Representative for weight data.
2. For leaving liquid temperature below 40°F(4.4°C) or above 60°F (15.6°C). Contact your nearest Quantech Sales Representative for application
requirements.