EasyManua.ls Logo

Record 5100 Series - Input;Output and Communication Settings; CAN-BUS Module Management; Input;Output Terminal Configuration

Default Icon
21 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operation mode >
SERVICE STG
Maintenance >
Functions >
Configure System
Learning System >
Parameter >
PARAMETER
Driving Cycle >
Time delay open >
Drive >
Entrance System >
Control Panel >
Locking >
LOCKING
Locking functions 2
Lock type
Start Delay 0
Closed VRR Error 0
Closing Force 0
Closed VRR Error
0 Disabled
1 Enabled
Closed VRR Error
0 Disabled
1 Enabled
Closed VRR Error
0 Disabled
1 Enabled
Closing Force
0
Briefly increases
closing force to
relieve locking bolt.
0=low force
40=high force
During Start Delay,
door is powered in
closing direction to
relieve any binding
on electric lock.
Operation mode >
SERVICE STG
Maintenance >
Functions >
Configure System
Learning System >
Parameter >
PARAMETER
CAN-BUS >
Input/Output >
Miscellaneous >
Entrance System >
Control Panel >
Locking >
CAN-BUS
FEM0 0
FEM1 0
FEM2 0
AKI1 0
S I1 0
AKI1 0
Any Can-Bus module or
sensor connected is
automatically identified &
displayed with a "1".
Disconnected units are
displayed with "?" and must
be removed manually with
FPC902. Not available units
are displayed with a "0".
Operation mode >
SERVICE STG
Maintenance >
Functions >
Configure System
Learning System >
Parameter >
PARAMETER
CAN-BUS >
Input/Output >
Miscellaneous >
Entrance System >
Control Panel >
Locking >
INPUT/OUTPUT
Ext. Sw IN 0
Emerg. Open/Close 0
EMERG, STOP Reset 0
STG >
FEM0 >
FEM1 >
Operation mode >
SERVICE STG
Maintenance >
Functions >
Configure System
Learning System >
Parameter >
PARAMETER
CAN-BUS >
Input/Output >
Miscellaneous >
Entrance System >
Control Panel >
Locking >
STG
AUX0_OUT 0
ZLP >
AUX0_IN 0
AUX1_IN 0
AUX4_IN 0
Configurable Input Terminals 4,6,and
18 on STG Control. Note: With
parameters identified as “Safety”, a
closed contact is required for normal
door operation.
AUX0_OUT: Dry contacts on STG to
Terminals 8(NO), 9(COM), 10(NC)
Rated @ 1 Amp 30VDC.
ZLP1: Additional Circuit Board to
connect threshold Safety Beams.
Set ELS to be active. See S5100
Parameter Settings record sheet.
Operation mode >
SERVICE STG
Maintenance >
Functions >
Configure System
Learning System >
Parameter >
PARAMETER
CAN-BUS >
Input/Output >
Miscellaneous >
Entrance System >
Control Panel >
Locking >
Operation mode >
SERVICE STG
Maintenance >
Functions >
Configure System
Learning System >
Parameter >
PARAMETER
CAN-BUS >
Input/Output >
Miscellaneous >
Entrance System >
Control Panel >
Locking >
FEM0,FEM1
contain settings
for input/outputs
for Expansion
Modules.
Ext. Sw IN;
INPUT/OUTPUT
Ext. Sw IN 0
Emerg. Open/Close 0
EMERG, STOP Reset 0
STG >
FEM0 >
FEM1 >
EMERG. OPEN/CLOSE
Function 0
Speed (Flip Flow only) 0
FUNCTION
0 Disabled
1 Emergency Open
2 Emerg. Close
Manual&RemSw
3 Emerg. Close
Locked
Five
options
listed.
Responds to AUX00_IN, AUX01_IN or AUX04_IN set to “2SoK_NSK and the control wired appropriately.
Ext. Sw IN
0 Ext. Sw IN
1 Inactive by 1 Way
5 Disabled
INPUT/OUTPUT
Ext. Sw IN 0
Emerg. Open/Close 0
EMERG, STOP Reset 0
STG >
FEM0 >
FEM1 >
and locked
Enable to comply with ANSI/BHMA A156.10for Exterior
sensor to be active in Exit mode and the door is open.

Related product manuals