Manual DFA 127 Full Power 12/2006 Rev. B Page 21 of 55
Commissioning
12.2 Checking the LEDs on the STG
Check LED 13 according to the table in chapter 13.
12.3 Checking the BDE functions and actuation devices
BDE position (permanently open)
1. Door must open and remain open
2. Check the movement characteristics
3. Door cannot be moved by hand when open
BDE position (locked)
1. Door must close
2. Check the movement characteristics
3. Check locking if present (see chapter 17 for status message for malfunction)
4. Pressing a second time initiates the SSK opening
5. SSK must release (if present)
6. AKI and AKA must not operate
BDE position (one-way traffic)
1. AKI and SSK must operate
2. AKA must not be triggered when the door is closed
12.4 Programming door speeds and hold-open times
The possibilities are described in chapter 13, operating instructions
12.5 Configuration of specific customer settings
The possibilities are described in chapter 15, configurations
All modifications must be entered on the configuration sheet (located in the op-
erator)