Commissioning
12.6 Safety check
1. BDE position (automatic mode)
2. Open door (e.g. with AKI)
3. Operate a safety device while closing. Door must re-open.
4. The same check must be performed with every safety device present.
12.7 Checking automatic reverse
1. Obstruct door while closing. The door must reverse. When the door next clo-
ses it moves at creep speed past the obstruction point.
2. Obstruct the door while opening. The door stops for hold-open time and clo-
ses. When the door next opens it moves at creep speed past the obstruction
point.
12.8 Touch control (push to actuate)
See about the configuration in chapter 15. By pressing lightly on the door, a
door-opening will be initiated.
12.9 Checking the functions of the DFA
Check all the DFA functions
Tighten the arm screw
12.10 Hand over to the client
Instruct the client
Hand over the operating manual
RESET demonstration