“10” - A negative going edge toggles the display between
“input” and “total” (from input to total, or vice versa).No
action is taken on the positive going edge.
“11” - A negative going edge zeros (tares) the input signal and
adds the value that was in the input display to the totalizer
value, every time this operation is performed. The
time-base, scale factor and low cut-out in “Module #5” are
in affect disabled, when this function is selected.
“12”- Display hold with tare. A negative going edge tares (zeros)
the input signal. Prior to the tare operation, the input signal is
saved and held (display hold) as long as the remote input pin
is low. On the positive edge, the input display will show
zero. If there is an increase to the input signal while the
remote input is low, the display will reflect (show) the
increase at the positive edge.
“13”- Instrument reading synchronization. A low level disables
all meter operations (alarms, total, analog out, etc.).A
positive edge resets the start of the A/D conversion, to allow
synchronization with external processes and controls. While
in this function, the other E-CON pin will be operational.
“14”- Print request. Transmits data according to the print options
that have been selected in Program Module #7. If the low
time exceeds 800 msec, a second print-out may occur.
“E2-CON”<>Ifthetotalizer option is installed, E2-CON has the same
programmable functions as E1-CON.
-14-