MODULE #9 - SERVICE OPERATIONS (Cont’d)
RESTORING ALL PROGRAMMING PARAMETERS BACK
TO FACTORY CONFIGURATION
All of the programming in Modules #1 through #8 can be restored back to
the factory configuration by entering a specific access code (refer to the
“Factory Configuration” section for the data that will be entered). The
procedure consists of entering “Pro 9”, keying-in “Code 66”, and then
pressing “P”. The IMD1 responds by displaying “INItAL” for several
seconds, and then returns to “Pro 0”.
Note: When this procedure is performed, all of the scaling, presets, etc. that
were programmed into the IMD1 will be overwritten.
“CodE” < > “66”
OPERATING THE IMD1
After completing input range selection, scaling and all set-up operations,
the unit is ready to install and operate. After power is applied, a display test
consisting of illuminating all segments for 2 seconds is performed. Afterward,
the input or total will appear, depending upon the display mode prior to the last
power-down. To switch the display to input, press “DOWN” (indicated by
“arrows” on the front panel) and to switch it to total, press “UP”.Ifthe
totalizer/linearizer option is not installed, then display switching to total is
inoperative. A minus sign “-” will precede numbers that are negative. If a
decimal point is chosen, one leading and one or more trailing zeros will
accompany the decimal point.
QUICK PROGRAMMING
To limit access to the set-up parameters, connect a key-switch or wire from
PGM. DIS. (TBA #3) to COMM. (TBA #5). With this pin connected to
common, only a predetermined amount of data can be viewed or altered, as
programmed by programming module #3. If “NO” was programmed for all of
the available steps in module #3, then pressing “P” will cause the unit to
display “Loc”. However, if “YES” was programmed in one or more of the
steps, then “P” will invoke entry into a series of commonly modified
parameters while protecting the crucial set-up information. This is referred to
as the “quick programming” mode. When “quick programming” mode is
entered, the alarms and hysteresis values can be modified in the same manner
as in the regular programming mode. The new alarm and hysteresis values will
take effect when “P” is pressed. The other operations in the “quick
programming” mode require special key sequences as shown:
To reset latched alarm, scroll through steps in “quick
programming” mode using the “P” button until “LAtCH1” or
“LAtCH2” appears in the display. If they do not appear, they are
not latched.
To reset: While “LAtCH1” or “LAtCH2” is being
displayed, press and hold “DOWN” and press
“P”. Pressing “P” alone causes a step to the next
item with no action taken on the alarm.
To reset peak and valley buffers, scroll through steps in “quick
programming” mode using the “P” button until “PEA” or
“VAL” appears in the display.
To reset: While “PEA” or “VAL” is being
displayed, press and hold “DOWN” and press
“P”. Pressing “P” alone causes a step to the next
item with no action taken on the buffer.
The front panel buttons are not only used to input data during the
programming and “quick programming” mode, but control a number of other
functions (if enabled in Pro “3”) as well. In the normal meter mode, these
functions are available:
To Switch to display of input: Press “DOWN” button.
To Switch to display of totalizer: Press “UP” button.
To re-zero input (tare): Press and hold “DOWN” and press “P”.
To reset totalizer to zero: Press and hold “UP” and press “P”.
To Enter programming or “quick programming”: Press “P”.
After each operation, a message will appear briefly to acknowledge the action.