PROGRAMMING EXAMPLE
As an example of a programming sequence, the following values, gained
from a process voltage application, are programmed into the indicator (±20
VDC range selected. Refer to “Selecting The Input Range” section).
DISPLAY: 0.0% @ 1 volt input, 100.0% at 5 volts input. Normal filtering.
Activate alarm #1 output when input falls below 80.0%, activate display
alarm. Peak and valley (max/min) reading for each day to be recorded.
TOTALIZER: Integrate (average) the input on a per-hour basis. When total
exceeds 50,000 then latch alarm #2. Alarm must be manually reset. Reset
alarm #2 by remote input. Disable totalization when input falls below 10.0%.
SERIAL: Provide hardcopy printout of total, input and peak/valley when
operator actuates print request. Baud rate 300.
ANALOG RE-TRANSMISSION: Output 4 mA @ 0.0% and 20 mA @
100.0%.
“Pro 1”.....Not required since scaling
done in “Pro 2”.
“Pro 2”.....“dECPNt” - Enter 0.0
“round” - Enter 0.1
“SCALE” - Enter yes
“dSP 1” - Enter 0.0
“INP 1” - Enter 1.000 V
“dSP 2” - Enter 100.0
“INP 2” - Enter 5.000 V
“SEGt” - Enter 1
“Pro 3”.....“dSP AL” - Enter yes
“ENt AL” - Enter yes
“dSPHYS” - Enter no
“rSt AL” - Enter no
“dSPbUF” - Enter yes
“rStbUF” - Enter yes
“SELdSP” - Enter yes
“rSttOt” - Enter yes
“tArE” - Enter no
“Pro 4”.....“FILtEr” - Enter 1
“E1-CON” - Enter 7 (reset alarm #2)
“E2-CON” - Enter 14 (print request)
“Pro 5”.....“tbASE” - Enter 2
“SCLFAC” - Enter 1.000
“Lo-cut” - Enter 10.0
“Pro 6”.....“trAc” - Enter no
“dISP” - Enter yes
“LAtC-1” - Enter no
“ASN-1” - Enter input
“AL-1” - Enter 80.0
“HyS-1” - Enter 0.1
“Act-1” - Enter LO
“LAtC-2” - Enter yes
“ASN -2” - Enter total
“AL-2” - Enter 5000.0
“HyS-2” - N/A
“Act-2” - Enter HI
“Pro 7”.....“bAud” - Enter 300
“AdrrES” - Enter 0
“Print” - Enter 6
“FULL” - Enter yes
“Pro 8”.....“ASIN” - Enter input
“AN-Lo” - Enter 0.0
“AN-HI” - Enter 100.0
-23-