EasyManua.ls Logo

Reer MOSAIC M1 - Division analysis: Enable threshold

Reer MOSAIC M1
266 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
8540780 • 25/01/2023 • Rev.43 181
English
Reading analysis: Enable threshold1 / threshold2
If you activate the options Enable threshold1 and/or Enable threshold2, the output
Out1 and/or Out2 are added to the graphical representation of the function block
and a number of additional parameters are displayed.
The following parameters are provided to define the behavior of the Threshold
comparator:
Threshold1 / threshold2: is the value of the threshold.
Hysteresis: is the hysteresis value
The following figure and table exemplify the states of the Enable threshold:
Figure 109 Example of Enable threshold behavior
Measurement value (A)
Current state of threshold
comparator
Next state of threshold
comparator
(A) < Threshold value - hysteresis
UNDER THRESHOLD
UNDER THRESHOLD
(A) <= Threshold value
UNDER THRESHOLD
UNDER THRESHOLD
(A) > Threshold value
UNDER THRESHOLD
OVER THRESHOLD
(A) < Threshold value - hysteresis
OVER THRESHOLD
OVER THRESHOLD
(A) < Threshold value - hysteresis
OVER THRESHOLD
UNDER THRESHOLD

Table of Contents