TIMER OPERATORS (max number = 32 with MOSAIC M1, 48 with MOSAIC M1S,
MOSAIC M1S COM)
TIMER operators allow you to generate a signal (TRUE or FALSE) for a user-definable period.
MONOSTABLE
The MONOSTABILE operator generates a level 1 (TRUE)
output activated by the rising edge of the input and
remains in this condition for the set time.
Parameters
Time: The delay can be set to between 10 ms and
1098,3 s.
Scale: The user can choose two different scales for the time T to be set.
10 ms...60 s, step 10 ms
60,1 s...1098,3 s, step 100 ms
Rising edge: If selected, the output is set to 1 (TRUE) on the input signal's rising edge where
it remains for the set time, which can be extended for as long as the input stays at 1 (TRUE).
In
Out
T T T
If not selected the logic is inverted, the output is set to 0 (FALSE) on the input signal's
falling edge, where it remains for the set time, which can be extended for as long as the
input stays at 0 (FALSE).
In
Out
T T T
Retriggerable: If selected the time is reset each time the input status changes.
Rising edge
T = set time
Falling edge
T = set time