MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
90 8540780 • 25/01/2023 • Rev.43
English
MO2 / MO4 (Figure 46)
MEANING
LED
REMEDY
RUN
IN FAIL
EXT FAIL
SEL0/1
OSSD1...4
CLEAR1...4
STATUS1...4
GREEN
RED
RED
ORANGE
RED/GREEN
YELLOW
YELLOW
Internal fault
OFF
2 or 3
flashes
OFF
Shows the
physical
address of the
unit
Red
OFF
OFF
Return the unit to
ReeR to be repaired
Compatibility error
OFF
5
flashes
OFF
5
flashes
5
flashes
5
flashes
Firmware version
not compatible
with MOSAIC M1,
return to ReeR for
FW upgrade.
OSSD output error
OFF
4
flashes
OFF
4 flashes
(only the LED
corresponding to
the output in FAIL
mode)
OFF
OFF
Check OSSD1/2
connections
If the problem
persists, return the
unit to ReeR to be
repaired
Error in communication
with master
OFF
5
flashes
OFF
OFF
OFF
OFF
Restart the system
If the problem
persists, return the
unit to ReeR to be
repaired
Error on other
slave or MOSAIC M1
OFF
ON
OFF
OFF
OFF
OFF
Restart the system
Check which unit is
in FAIL mode
Same type of slave
with same address
detected
OFF
5
flashes
5
flashes
OFF
OFF
OFF
Change the unit's
address (see
NODE SEL)
Power supply missing
on OSSD 3,4 (MO4 only)
ON
OFF
ON
Red
flashes
flashes
OUTPUT
condition
Connect 13 and 14
pin to power
supply
Status output overload
or short circuit
OFF
OFF
ON
OUTPUT condition
CLEAR
condition
flashes
Check STATUS
connections
Error on node
detection circuit
OFF
3
flashes
OFF
3
flashes
OFF
OFF
OFF
Return the MO2/4
to ReeR to be
repaired
Table 73 - Troubleshooting MO2/MO4
Figure 46 - MO2 / MO4