MI8O2 (Figure 41)
Table 68 - Troubleshooting MI8O2
Figure 41 -
MI8O2
MEANING
LED
REMEDY
RUN
IN FAIL
EXT FAIL
SEL0/1
IN1...8
OSSD1/2
CLEAR1/2
STATUS1/2
GREEN
RED
RED
ORANGE
YELLOW
RED/GREEN
YELLOW
YELLOW
Internal fault
OFF
2 or 3
flashes
OFF
Shows the
physical
address of the
unit
OFF
Red
OFF
OFF
Return the unit to ReeR
to be repaired
Compatibility error
OFF
5
flashes
OFF
5 flashes
5
flashes
5
flashes
5
flashes
Firmware version not
compatible with
MOSAIC M1, return to
ReeR for FW upgrade.
OSSD output error
OFF
4
flashes
OFF
OFF
4 flashes
(only the LED
corresponding to the
output in FAIL mode)
OFF
OFF
Check OSSD1/2
connections
If the problem persists,
return the unit to ReeR
to be repaired
Error in
communication with
master
OFF
5
flashes
OFF
OFF
OFF
OFF
OFF
Restart the system
If the problem persists,
return the MI8O2 to
ReeR to be repaired
Error on other
slave or MOSAIC M1
OFF
ON
OFF
OFF
OFF
OFF
OFF
Restart the system
Check which unit is in
FAIL mode
Same type of slave
with same address
detected
OFF
5
flashes
5
flashes
OFF
OFF
OFF
OFF
Change the unit's
address (see NODE
SEL)
Node detection
circuit error
OFF
3
flashes
OFF
3
flashes
OFF
OFF
OFF
OFF
Return the unit to ReeR
to be repaired