MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
8540780 • 25/01/2023 • Rev.43 91
English
MO4L (Figure 47)
MEANING
LED
REMEDY
RUN
IN FAIL
EXT FAIL
SEL0/1
OSSD1...4
STATUS/RST/FBK 1...4
GREEN
RED
RED
ORANGE
RED/GREEN/YELLOW
YELLOW
Internal fault
OFF
2 or 3
flashes
OFF
Shows the
physical
address of the
unit
Red
OFF
Return the unit to ReeR to
be repaired
Compatibility error
OFF
5
flashes
OFF
5
flashes
5
flashes
Firmware version not
compatible with
MOSAIC M1, return to ReeR
for FW upgrade.
OSSD output error
OFF
4
flashes
OFF
4 flashes
(only the LED corresponding
to the output in FAIL mode)
OFF
Check OSSD1/2 connections
If the problem persists,
return the unit to ReeR to
be repaired
Error in communication
with master
OFF
5
flashes
OFF
OFF
OFF
Restart the system
If the problem persists,
return the MO4L to ReeR to
be repaired
Error on other
slave or Master
OFF
ON
OFF
OFF
OFF
Restart the system
Check which unit is in FAIL
mode
Same type of slave
with same address
detected
OFF
5
flashes
5
flashes
OFF
OFF
Change the unit's address
(see NODE SEL)
Overload on OSSD /
OSSD load connected
to 24V
ON
OFF
ON
Shows the
physical
address of the
unit
Red blinking
(only LED corresponding to
the relative output)
OUTPUT
state
Verify OSSD connections
Short circuit or
overload detected on
status output
ON
OFF
ON
Shows the
physical
address of the
unit
OUTPUT
state
blinking
Verify output status
connections
Table 74 - Troubleshooting MO4L
Figure 47 - MO4L