MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
8540780 • 25/01/2023 • Rev.43 79
English
MV0, MV1, MV2 (Figure 35)
MEANING
LED
RUN
IN FAIL
EXT FAIL
SEL0/1
ENC*
PROX
SH
GREEN
RED
RED
ORANGE
YELLOW
YELLOW
YELLOW
Power on - initial TEST
ON
ON
ON
ON
ON
ON
ON
Table 57 - Opening screen
MEANING
LED
RUN
IN FAIL
EXT FAIL
SEL0/1
ENC*
PROX
SH
GREEN
RED
RED
ORANGE
YELLOW
YELLOW
YELLOW
NORMAL OPERATION
OFF
if the unit is waiting
for the first
communication
from the MASTER
FLASHES
if no INPUT or
OUTPUT requested
by the
configuration
ON
if INPUT or OUTPUT
requested by the
configuration
OFF
operation OK
OFF
operation OK
Shows the
NODE_SEL0/1
signal table
ON
Encoder
connected and
operative
ON
Proximity
connected and
operative
OFF
Axis in normal
speed range
ON
Axis in stand
still
BLINKING
Axis in
overspeed
Table 58 - Dynamic screen
* NOT PRESENT ON MV0 MODULE
Figure 35 - MV1, MV2