MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
8540780 • 25/01/2023 • Rev.43 97
English
MO4LHCS8 (Figure 53)
MEANING
LED
REMEDY
RUN
IN FAIL
EXT FAIL
SEL 0/1
OSSD 1...4
CLEAR1...4
STATUS1...8
GREEN
RED
RED
ORANGE
RED
GREEN
YELLOW
YELLOW
Internal fault
OFF
2 / 3
flashes
OFF
Shows the
physical
address of
the unit
Rosso
OFF
Return the unit to ReeR
to be repaired
Compatibility error
OFF
5
flashes
OFF
5
flashes
5
flashes
5
flashes
Firmware version not
compatible with
MOSAIC M1, return to
ReeR for FW upgrade.
OSSD output error
OFF
4
flashes
OFF
4 flashes
(only the LED
corresponding to the
output in FAIL mode)
OFF
OFF
If the problem persists,
return the module to
ReeR to be repaired
Error in
communication
with master
OFF
5
flashes
OFF
OFF
OFF
OFF
Restart the system
If the problem persists,
return the module to
ReeR to be repaired
Error on other
slave or
MOSAIC M1
OFF
ON
OFF
OFF
OFF
OFF
Restart the system
Check which unit is in
FAIL mode
Same type of slave
with same address
detected
OFF
5
flashes
5
flashes
OFF
OFF
OFF
Change the unit's
address
(see NODE SEL)
Short circuit or
overload detected
on status output
ON
OFF
ON
OUTPUT
condition
CLEAR
condition
flash
Verify output status
connections
OSSD overload or
load connected to
24VDC
ON
OFF
ON
Blinking (only LED
corresponding to the
relative output)
OFF
OUTPUT
condition
Verify OSSD connections
Power supply
missing on
OSSD3-OSSD4
ON
OFF
ON
OSSD3/OSSD4
led blinking
OSSD3/OSSD4
led blinking
OUTPUT
condition
Connect pin 14 to
24VDC
Error on node
detection circuit
OFF
3 flashes
OFF
3
flashes
OFF
OFF
OFF
Return the module to
ReeR to be repaired
Table 80 - Troubleshooting MO4LHCS8
Figure 53 -
MO4LHCS8