EasyManua.ls Logo

Reer MOSAIC M1 - MI8 O4 Module; MI8 - MI16 Modules; MI12 T8 Module

Reer MOSAIC M1
266 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
54 8540780 • 25/01/2023 • Rev.43
English
MI8O4 module
PFH
d
(IEC 61508:2010)
1,32E-8
SFF
99,7%
Rated voltage
24VDC 20%
Dissipated power
3W max
Digital INPUTS (No./description)
8 / PNP active high according to EN 61131-2
INPUT FBK/RESTART (No./description)
Up to 4 / EDM control / possible Automatic
or Manual operation with RESTART button
Test OUTPUT (No./description)
4 / to check for short-circuits - overloads
SIL 1/PL c OUTPUTS (No./description)
Up to 4 / programmable - PNP active high
OSSD (No./description)
4 single / solid state safety outputs:
PNP active high 400mA@24VDC max
Interface type C class 3 (ZVEI CB24I)
Connection to MOSAIC M1S,
MOSAIC M1S COM
via MSC 5-way ReeR proprietary bus
MI8 - MI16 modules
Model
MI8
MI16
PFH
d
(IEC 61508:2010)
4.46E-9
4.93E-9
SFF
99,7%
99,8%
Rated voltage
24VDC 20%
Dissipated power
3W max
Digital INPUTS (No./description)
8
16
PNP active high according to EN 61131-2
Test OUTPUT (No./description)
4 / to check for short-circuits - overloads
Connection to MOSAIC M1 and
MOSAIC M1S, MOSAIC M1S COM
via MSC 5-way ReeR proprietary bus
MI12T8 module
PFH
d
(IEC 61508:2010)
5,60E-9
SFF
99,7%
Rated voltage
24VDC 20%
Dissipated power
3W max
Digital INPUTS (No./description)
12
PNP active high according to EN 61131-2
Test OUTPUT (No./description)
8 / to check for short-circuits - overloads
Connection to MOSAIC M1 and
MOSAIC M1S, MOSAIC M1S COM
via MSC 5-way ReeR proprietary bus