5-22 Instructions for Use Rexroth EcoDrive 03 DKC**.3-040...200
DOK-ECODR3-DKC40*200UL-IB01-EN-P
Only use well-sealed control cabinets so that moisture condensation
cannot arise as a result of warm and moist external air entering the
cabinet.
In the event that control cabinets are operated with the doors open
(commissioning, servicing etc.) it is essential to ensure that after the
doors are closed the drive controllers cannot at any time be cooler than
the air in the control cabinet, as otherwise moisture condensation can
occur. For this reason sufficient circulation must be provided inside the
control cabinet to avoid pockets of heat.