Rinnai I-Series Condensing Boiler Combi Manual 103
700
PC Board
• PC Board circuit error.
• Replace PC Board.
710
Solenoid Valve Circuit
• Ensure Dip switch 5 on the PC Board is in
the OFF posion (default).
• Ensure the gas control wire is not loose or
damaged.
• Replace the PC Board.
720
Flame Rod
• Check the ame rod and wire for damage.
• Ensure the ame rod and wire are not wet.
• If there is no issue with the ame rod or
wiring, replace the PC Board.
890
Freeze Issue
• The boiler checks the heat exchanger
temperature at the me of operaon.
• If the temperature is too low, an error will
occur.
• Check if there is freezing in the boiler or
CH system.
999
PC Board Mismatch
• This code occurs when the PC Board and
the internal logic do not match.
• Check if the soware versions of the board
and operaon board do not match.
LC
Scale Buildup in Heat Exchanger
• Flush the DHW plate heat exchanger.
• The LC code will reset automacally when
scaling is removed. If the LC code remains,
check the DHW thermistor, ow sensor or
boiler pump.
FFF
Maintenance Indicator
• This code is a placeholder in diagnosc
code history indicang a service provider
performed maintenance or service.
• Enter this code aer performing service by
pressing and holding the Up buon, then
press and hold the Down buon, and then
press the DHW buon simultaneously. FFF
will appear on the display.
No
Code
Nothing happens when DHW water ow is
acvated
• Verify the minimum ow rate required
to re the boiler is seen.
• Measure the resistance of the ow
control sensor.*
• Clean the inlet water supply lter.
• On new installaons, ensure the hot and
cold water lines are not reversed.
• Conrm the inlet water temperature is
not too high.
• Ensure the integrated boiler pump
operates properly.
• Ensure the DHW operaon switch is on.
No
Code
Decreasing or uctuang DHW water ow
volume
• Ensure the gas pressure is proper.
• Ensure the water pressure is proper.
• Ensure the inlet water lter for DHW is
clean.
• Ensure there is not lime scale buildup
present.
• Ensure the vent and vent sengs are
properly set up.
• If a DHW recirculaon system is used,
the DHW ow volume may vary slightly.
• Ensure all air has been purged from the
system.
• Ensure the pump is set to speed 3.
• During simultaneous CH and DHW
operaon mode, it is possible to see
decreased DHW ow.
No
Code
Fluctuang DHW outgoing temperature
• Ensure the gas pressure is proper.
• Ensure the water pressure is proper.
• Ensure the DHW thermistor, ow servo,
and bypass servo are in good condion.
• Ensure the inlet lter for DHW is clean.
• If a DHW recirculaon system is used,
the DHW temperature may vary slightly.
• Ensure all air is removed from the
system.
No
Code
Boiler does not start heang with a heang
demand present
• Supply temperature or return
temperature inside the boiler may be
too hot.
• Ensure the pump operates properly.
• If there is a demand immediately aer
using DHW, wait at least three minutes
for operaon.
* See “Electrical Diagnoscs” on Technical Data
Sheet located on inside front cover of boiler.
Up and Down
E;FFF
Press the DHW
buon