Rinnai I-Series Condensing Boiler Combi Manual 43
Combuson air provided to the appliance should not be taken from any area of the structure
that may produce a negave pressure (i.e. exhaust fans, powered venlaon fans).
Locaon
To maintain proper circulaon of combuson air two permanent openings (one upper, one lower)
must be posioned in conned spaces. The upper shall be within 12 in. (0.30 m) of the top of the
conned space and the lower opening shall be within 12 in. (0.30 m) of the boom of the conned
space. Openings must be posioned as to never be obstructed.
12 in.
(300 mm)
10 in.
(250 mm)
Verify all combuson air opening sizes are correct.
Ensure that the Combuson Air Requirements are followed that will provide sucient
combuson air for the appliance.
DO NOT use room air for combuson in applicaons where the indoor air is corrosive.
Verify that adequate combuson air is available for all appliances installed in the space.
Installaon complies with Naonal Fuel Gas Code, ANSI Z223.1/NFPA 54 as well as local
and state regulaons therein.
To prevent possible personal injury or death due to asphyxiaon, common venng with other
manufacturers induced dra appliances is not allowed.
IMPORTANT
WARNING

Table of Contents

Other manuals for Rinnai I Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rinnai I Series and is the answer not in the manual?

Rinnai I Series Specifications

General IconGeneral
BrandRinnai
ModelI Series
CategoryBoiler
LanguageEnglish

Related product manuals