Rinnai I-Series Condensing Boiler Combi Manual 43
Combuson air provided to the appliance should not be taken from any area of the structure
that may produce a negave pressure (i.e. exhaust fans, powered venlaon fans).
Locaon
To maintain proper circulaon of combuson air two permanent openings (one upper, one lower)
must be posioned in conned spaces. The upper shall be within 12 in. (0.30 m) of the top of the
conned space and the lower opening shall be within 12 in. (0.30 m) of the boom of the conned
space. Openings must be posioned as to never be obstructed.
12 in.
(300 mm)
10 in.
(250 mm)
□
Verify all combuson air opening sizes are correct.
□
Ensure that the Combuson Air Requirements are followed that will provide sucient
combuson air for the appliance.
□
DO NOT use room air for combuson in applicaons where the indoor air is corrosive.
□
Verify that adequate combuson air is available for all appliances installed in the space.
□
Installaon complies with Naonal Fuel Gas Code, ANSI Z223.1/NFPA 54 as well as local
and state regulaons therein.
To prevent possible personal injury or death due to asphyxiaon, common venng with other
manufacturer’s induced dra appliances is not allowed.