Rinnai I-Series Condensing Boiler Combi Manual 85
Parameter
Number
Seng Descripon
Selecon
A b C d
00
Pressure Indicaon on the Control Panel
Yes No
The current pressure will cycle on the controller
display. If an external pressure gauge is present,
it is permissible to change the seng to "No."
01
Outdoor Reset Curve
Curve
1
Curve
2
Curve
3
Curve
4
This parameter is available when Dip Switch 1 is
in the OFF (default) posion. Select the proper
curve from below. See secon “12.5 Outdoor
Reset Control” for more informaon.
Curve 1: Standard baseboard, high eciency air
handler, cast iron or panel radiators.
Curve 2: Staple up radiant.
Curve 3: High temperature air handler or
undersized baseboard.
Curve 4: Custom curve based on customer
input.
02
Boost
No
30
Minutes
60
Minutes
This parameter is available when Dip Switch 1 is
in the OFF (default) posion.
Boost mode works when the outdoor sensor
detects higher outdoor temperatures than
expected.
03
Maximum Outdoor Temperature the Boiler will
Fire in CH Mode
No
Maximum
77°F
(25°C)
This parameter is available when DIP switch 1 is
in the OFF (default) posion.
This sets the maximum outdoor temperature
the boiler will re in CH mode. This can prevent
the boiler from ring in warm outdoor
temperatures.
10
Maximum DHW Set Point Temperature
120°F
(49°C)
140°F
(60°C)
This selects the maximum DHW set point
temperature. When 140°F, it is recommended
to have a mixing valve to prevent scalding.
11
How Long Diverter Valve in DHW Posion
3
Minutes
10
Seconds
This selects the length of me the 3 Way Valve
will stay in the DHW posion aer using DHW
even if a CH demand is present.
While the 3 Way Valve is in the DHW posion,
this enables quicker delivery of hot water.
12
DHW Recirculaon Piping Setup
Crossover
Valve
Dedicated
Return
This parameter is available when DIP switch 3 is
in the ON posion. This sets the DHW
recirculaon piping mode, which controls the
circulaon logic. Ensure this corresponds to the
DHW recirculaon piping.