86 Rinnai I-Series Condensing Boiler Combi Manual
14
CH Temperature Limitaon During
Simultaneous Operaon
Yes No
This parameter is available when DIP switch 3 or
4 is in the ON posion.
This enables the CH temperature seng to be
limited during simultaneous DHW and CH
operaon. This can prevent unintenonally
supplying high temperature DHW to low
temperature CH applicaons.
During simultaneous operaon, supply
temperature may be up to 180°F. When
selecng "NO" limitaon, ensure that the CH
system and heang applicaon is designed for
this temperature.
15
3 Way Valve Posion During Simultaneous
Operaon
Normal
Addional
CH
This parameter is available when DIP switch 3 or
4 is in the ON posion.
This adjusts the 3 Way Valve posion to open
the CH side more for when the ow of the CH
side is reduced due to DHW demand. This may
restrict the DHW capacity.
16
LC Check
Available
No
Detecon
This seng enables the boiler to check for lime
scale condions in the DHW side of the plate
heat exchanger. When detecng lime scale, an
LC error code will appear on the display. Once
lime scale is removed by ushing the plate heat
exchanger, the LC code will disappear.
17
Adjust DHW Temperature Seng
0°F
(0°C)
1.8°F
(1°C)
3.6°F
(2°C)
5.4°F
(3°C)
This seng enables the DHW output
temperature to be adjusted without adjusng
the set point temperature.
13
DHW Recirculaon with Timer Relay Input
Yes No
This parameter is available when DIP switch 3 is
in the ON posion. This enables an external
mer to also control the ming for DWH
recirculaon to more directly correspond to the
customers needs.
Parameter
Number
Seng Descripon
Selecon
A b C d