CAUTION
After conrmation of the above conditions, follow these guidelines when performing wiring:
•
•
•
• Conrm that electrical capacity is sucient.
• Conrm that the cable thickness is as specied in the power source specications.
• Always install an earth leakage circuit breaker in wet or moist areas.
• The following can be caused by a drop in voltage: vibration of a magnetic switch,
damaging the contact point, broken fuses, and disturbance of normal functioning.
• Conrm that starting voltage is maintained at more than 90 percent of the rated voltage
marked on the name plate.
• Before accessing terminals, all supply circuits must be disconnected.
• Disconnection from a power supply must be incorporated into the xed wiring. It must
have an air gap contact separation of at least 3mm in each active (phase) conductors.
Model I
L2
L1
LPPUS REWOP Y
1(A)
2(A)
3(A)
1(B)
2(B)
3(B)
1(C)
2(C)
3(C)
1(D)
2(D)
3(D)
1(E)
2(E)
3(E)
TO A
TO B
TO D
TO E
TO C
OPTIONAL
OPTIONAL
OPTIONAL
OPTIONAL
OPTIONAL
OPTIONAL
Model K
L2
L1
LPPUS REWOP Y
L1(A)
L2(A)
S(A)
L1(B)
L2(B)
S(B)
L1(C)
L2(C)
S(C)
L1(D)
L2(D)
S(D)
L1(E)
L2(E)
S(E)
TO A
TO B
TO D
TO E
TO C
OPTIONAL
OPTIONAL
OPTIONAL
OPTIONAL
OPTIONAL
OPTIONAL
Model J
L2
L1
LPPUS REWOP Y
L1(A)
L2(A)
S(A)
L1(B)L
2(B)
S(B)
L1(C)
L2(C)
S(C)
L1(D)
L2(D)
S(D)
L1(E)
L2(E)
S(E)
TO A
TO B
TO D
TO E
TO C
OPTIONAL
OPTIONAL
OPTIONAL
OPTIONAL
OPTIONAL
OPTIONAL
Wiring
the circuit diagram posted on the inside of the control cover.
transporation. Because loose screws may cause wire burn-out, check that the screws are
tightly fastened.
To satisfy the EMC compulsory regulations, which is required by the international standard
correct magnetic rings on your equipment according to the wiring diagram that adheres to
your equipment .