EasyManua.ls Logo

Rockwell Automation Allen-Bradley 1769-L24ER-QB1B

Rockwell Automation Allen-Bradley 1769-L24ER-QB1B
332 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
220 Rockwell Automation Publication 1769-UM021I-EN-P - May 2018
Chapter 8 Use I/O Modules with CompactLogix 5370 L2 Controllers
Power Supply Distance Rating
In a CompactLogix 5370 L2 control system, you can install Compact I/O
modules on as local expansion modules to the right of the controller system.
Compact I/O modules each have a power supply distance rating that you must
consider before you install them.
Power supply distance rating is the number of slots a Compact I/O module can
be installed away from the power supply. If a Compact I/O module has a
distance rating of three, you can include up to two modules between the
Compact I/O module and the power supply.
Additionally, the controller has embedded I/O modules that are designed to
protect against installation of a Compact I/O module directly to the right of
the embedded power supply. CompactLogix 5370 L2 control systems have
embedded I/O modules in the controller. CompactLogix 5370 L2 control
systems have one or two embedded I/O modules as described as follows:
1769-L24ER-QB1B controller - One embedded I/O module
1769-L24ER-QBFC1B and 1769-L27ERM-QBFC1B controllers -
Two emb edded I/O modules
The embedded I/O modules are not considered local expansion modules.
However, you must still include each embedded I/O module in the module
slot count when determining where to install Compact I/O module as a local
expansion module.
Because CompactLogix 5370 L2 control systems only allow up to four local
expansion modules in the system, you can install most Compact I/O modules
in any local expansion module slot. Some Compact I/O modules have power
supply distance ratings that affect where you can install them in the
CompactLogix 5370 L2 control system.