170 Rockwell Automation Publication 20D-PM001D-EN-P - March 2019
Appendix B Application Notes
Figure 9 - Sleep-Wake Mode Flow Chart
Is Sleep-Wake
Working?
Have these conditions been met?
Is Required Input Closed?
(Stop, Enable, Run)
Did a Drive
Fault Occur?
Which Required Input
was Chosen?
Meet all Conditions!
Close Input
Reset Fault
Ye s
Ye s
Stop or Enable
Run
Ye s
Ye s
Drive Running?
No
DirectInvert
No
No
No
No
No
No
Issue a Start Command
(HIM, Network or TB)
Open & Close Input
Consult Factory
No
Consult Factory
Which Mode is Selected?
"Invert" or "Direct"
1. [Sleep-Wake Ref] must be set to the analog input that will control
"Start/Stop" functions.
2. [Sleep-Wake Mode] must = "1, Direct" (Enable) or "2, Invert (Enable)."
3. [Sleep Level] must be less than [Wake Level] in Direct mode (or
greater than [Wake Level] in "Invert" mode).
4. [Speed Ref x Sel] must be set to a speed reference source that will
control the drive. If [Sleep-Wake Ref] = [Speed Ref x Sel], the same
analog signal will control
start/stop and speed reference.
5. At least one of the following must be programmed for [Dig Inx Sel]:
"Normal Stop," "Enable," "Start," "Run."
Is Analog Signal
Greater
than or equal to [Wake Level]?
and for time period greater than
or equal to [Wake Time]
Ye s Ye s
Is Analog Signal
Less
than or equal to [Wake Level]?
and for time period greater than
or equal to [Wake Time]
Increase Analog Input
Signal and wait for a time
period greater than or
equal to [Wake Time].
Decrease Analog Input
Signal and wait for a time
period greater than or
equal to [Wake Time].
Was a Stop Issued?
or
Power Cycled?