P
o
w
S
upp
l
y
NG
M
O
Repair
8.4 General Troubleshooting
Type of fault
Fault diagnose
Fault rectification
NGMO2 does not
deliver output voltage
on both channels
Fuse blown by overvoltage at
the power supply input.
LEDs for operating voltage on
processor board do not light
(see section 8.3.1).
Fault still present.
Replace defective fuses.
Replace processor board as
described in section 9.1.4.
Return the NGMO2 to the
Support Service Centre (see
chapter 2).
NGMO does not
deliver output voltage
on one channel
On one power supply unit the
corresponding fuses have been
blown by overvoltage at the
power supply input.
LEDs for operating voltage
assigned to one of the mains
supply units on the processor
board do not light (see section
8.3.1).
LEDs for operating voltage on
one of the processor boards do
not light (see section 8.3.1).
Fault still present.
Replace defective fuses.
Replace processor board as
described in section 9.1.4.
Replace the corresponding
analog board as described in
section 9.1.2.
Return the NGMO2 to the
Support Service Centre (see
chapter 2).