7.2 Parameters
1. Keep the UP and DOWN keys pressed simultaneously for 3 seconds until the first
programming variable appears on display. A confirmation buzzer is emitted upon menu access.
2. Select the variable to be modified using the UP or DOWN key.
3. Now modify the value by keeping the SET key pressed and pressing the UP or DOWN keys.
4. Keep the UP or DOWN keys pressed (or wait 30 seconds without pressing any key) until the
operation state (OFF or ON) appears on display, to exit the menu once setting is completed.
A confirmation buzzer is emitted upon menu exit.
5. The modifications made to the variables will be automatically memorized when exiting the
configuration menu.
Defrosting is cyclically performed every 120 minutes, with a 6 minute duration, for
dehumidifiers with cold integration. These timings are default settings.
7.3 Other functions
7.3.1 Manual activation of defrosting
Defrosting can be manually activated by pressing the key for more than 3 seconds, if the
activation conditions (temperature read by defrosting probe below 5°C) exist; a confirmation
buzzer will follow.
Defrosting is in this way activated by switching off the compressor and leaving the fan on.
7.3.2 Manual forcing of defrosting end
Pressing the key for 3 seconds during defrosting, forces defrosting end; a confirmation buzzer
will follow.
This function cannot be activated within the programming menu.
The compressor activates:
0= humidistat input present or room
temperature > SEc
1= humidistat input present
2= room temperature > SEc
3= humidistat input present and
room temperature > SEc