Ecodry IN+ CN+ - Manual of installation, use and maintenance
5. Technical data
5.1 Table of technical data and operating limits
Units with neutral air also work without refrigerator water. However, the outlet air from the unit
will, in this case, be warmer than the inlet air and the dehumidifier yield simultaneously
decreases. This possibility is particularly useful in the mid-season periods, during which a
thermal intake to the environment is welcome.
The dehumidification power is stated in the nominal point 26°C, 65% relative humidity with
water supply from refrigerator at 15°C.
The dehumidification power will suffer variations that, in other conditions, can also be
significant, the further away from the nominal conditions.
5.2 Operation limits
5.3 Air ow and pressure
Wall
Wall
Ceiling
Ceiling
Ceiling
Ceiling
IN+300
IN+300DC
CN+300
CN+300DC
CN+600
CN+600DC
Dehumidification capacity
l/day
20,8
48
Cooling capacity
W
/
1240
/
1240
/
3230
Absorbed power
W
320
700
Absorbed current
A
2,15
5
Electrical supply
V/ph/Hz
230/1+N/50
Tollerance of electrical supply
%
+/- 10
Air flow
m
3
/h
250
600
Useful static head
Pa
40
150
Nominal water flow
l/ora
150
500
Water pressure drop
kPa
15
30
29
Limit storage temperature
°C
-10/+43
Limit storage humidity
%ur
90
Sound pressure level
db(A)
38
43
Weight
kg
34
36
35
37
52
55
Temperature of internal air [°C]
Humidity of internal air [%]
Ecodry IN+CN+_20190801 Page di Rossato Group Srl21 43