FA ROTEX Solaris RPS4 - 06/2015
6 x Control
6.3.1 Display during start-up
After switching on, the Solaris R4 controller performs a self-test
where the display elements are actuated in a targeted manner
and the setting parameters of the user level are displayed. The
following testing steps are carried out, and the results displayed
for about 2 seconds (fig. 6-5):
– Immediately after switching on, the start display appears
which shows the installed software version and the serial
number of the device.
– During initial commissioning, the desired display language is
queried.
– After this, the current parameter settings which the user can
change are displayed.
– When the operating display appears, the self test is complete.
– The functions of the solar operating pump P
S
and their oper-
ating status lights can only be tested manually, for safety rea-
sons (see section 6.2.6).
Parameter Designation Value range Resolution Remark
T
K
max
Max. measured collector tem-
perature
-30 to 250 °C 1 K –
T
K
min
Min. measured collector tem-
perature
-30 to 250 °C 1 K –
V max Maximum flow rate
0.0 to 12.0 l/min
0.1 l/min Maximum flow measured during filling
0.0 to 20.0 l/min
0.0 to 40.0 l/min
0.0 to 100.0 l/min
PS Peak output 0,0 to 99.9 kW 0.1 kW Maximum value from 5 min output average
PS (15h) Peak value of the day 0,0 to 99.9 kW 0.1 kW
Maximum value of the peak output within the
last 15 hours
W (15h) Daily thermal yield 0.0 to 999.9 kW 0.1 kWh Thermal yield within the last 15 hours
W Total thermal yield
0.0 to 9999.9 kWh
or 10.000 to
99.999 MWh
to 0.1
0.001 kW
Total solar thermal yield determined from the
momentary output
P Momentary output 0,0 to 99.9 kW 0.1 kW Mean value during the last minute
DT Target spread 1 to 15 K 1 K
Nominal temperature difference T
V
–T
R
at mod-
ulation operation (calculated)
P1 Output stage in normal mode 0 to 100 % 1 % –
Min. stage
Smallest released output stage
P1
1 to 10
0 to 100 %
1; 1 % Only accessible for an expert (see fig. 6-7)
Stage ‘On’
Running time for the solar oper-
ating pump P
S
0 to 99999 h 1 h Only accessible for an expert (see fig. 6-7)
VAR
Variable step width for opti-
mised switch-on condition
0 to 10 1 K –
Tab. 6-3 Info parameter (maximum values and calculated values)
Fig. 6-5 Display during start-up