EasyManua.ls Logo

Saftronics FP5/GP5 Series - 6.10 MEMOBUS Control; 6.10.1. Communication Specifications; 6.10.2. Data to be Sent;Received by Communication

Saftronics FP5/GP5 Series
108 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 6: Programming Features
Firmware – S2011 and S3012
Revision: 1 (9/98) 60 © Saftronics, Inc.
§ Step Voltage of Tuning (n100, n101)
Sets voltage variation width of one tuning cycle. Setting is made in a percentage of motor rated voltage. By
increasing this value, the rotating speed variation becomes larger. This voltage variation width is set when starting
tuning voltage is 100% and motor rated voltage is 5%. Values obtained by linear interpolation are set to any voltage
values other than these values.
Figure 51 Energy Saving Voltage Variation Width
6.10 MEMOBUS Control
FP5/GP5 can perform serial transmission by using a Programmable Controller (PLC) and MEMOBUS communication. MEMOBUS
is composed of one master PLC and 1 to 31 (maximum) slave units (FP5/GP5). In signal transmission (serial transmission)
between the master and slaves, the master always starts transmission and the slaves respond to it.
The master performs signal transmission with one slave at a time. Therefore, address numbers are assigned to each slave in
advance and the master specifies a number to perform signal transmission. The slave which receives the command from the
master executes the function and returns the response to the master.
6.10.1. Communication Specifications
Interface
: RS-485 (Communication interface card SI-K2/P must be mounted.)
Synchronization
: Asynchronous
Transmission parameter
:
Baud rate
: Selectable from 2400, 4800, 9600 BPS (Constant n107)
Data length
: Fixed to 8 bits
Parity
: Parity / no-parity, even / odd selectable (Constant n108)
Stop bit
: Fixed to 1 bit
Protocol
: In accordance with MEMOBUS
Maximum number of units
to be connected
: 31 units (when RS-485 is used)
6.10.2. Data to be Sent/Received by Communication
Data to be sent/received by communication are RUN commands, frequency reference, fault contents, Inverter status and
constant setting/reading.
§ Operation Mode Selection (n002)
Select the RUN command and frequency reference input method in constant n002. To provide a RUN command
and frequency reference by communication, set this constant to settings 4 to 8. Also, without regard to this selection,
monitoring of running status, constant setting/reading, fault reset and multi-function input command from the PLC are
enabled. The multi-function input command becomes OR with the command input from control circuit Terminals S2
to S6.
efesotomasyon.com - Control Techniques,emerson,saftronics -ac drive-servo motor

Table of Contents

Related product manuals