EB 8331-4 EN 19
Design and principle of operation
Safety
Motor switch-off By torque-dependent limit contacts
Degree of protection acc. to EN60529 IP54 with cable ducts
IP65 with cable glands (can be retrotted)
1)
Suspended mounting not permitted according to
EN60664
Overvoltage category II according to EN61010
Design and testing According to EN61010
Class of protection II according to EN61140
EMC Acc. to EN61000-6-2, EN61000-6-3 and EN61326
Degree of contamination 2 according to EN61010
Noise immunity According to EN61000-6-2
Noise emission According to EN61000-6-3
Environmental conditions
Mechanical environmental conditions Class 1M2 according to EN60721-3-1:1998
Class 2M1 according to EN60721-3-2:1998
Class 3M4 according to EN60721-3-3:1998
Class 4M4 according to EN60721-3-4:1998
Permissible temperatures
2)
Ambient 5 to 60°C
Storage –25 to +70°C
Ambient conditions
Humidity 5 to 95% relative humidity, no dew formation
Compliance
·
Additional electrical equipment
Limit contacts Mechanical
Two adjustable limit contacts with changeover switches;
230VAC/1A · Without contact protection
Electronic Two adjustable limit contacts with relay and changeover
switches;
230VAC/1A · Without contact protection
RS-485 module (order no. 1402-1522) Module for Modbus-RTU communication
1)
Cable glands M20x1.5 with metal nut SW 23/24 (order no. 1400-8828)
2)
The permissible medium temperature depends on the valve on which the electric actuator is
mounted. The limits in the valve documentation apply.