EasyManua.ls Logo

Samson 3374-10 - Excerpt from Modbus List

Samson 3374-10
104 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EB 8331-4 EN 93
Decommissioning and disassembly
17.2.8 Excerpt from Modbus list
The electric actuator in rmware version 3.10 and higher can be tted with an RS-485 mod-
ule to use the Modbus-RTU protocol. This protocol is a master/slave protocol. In this case, a
control station is the master and the electric actuator the slave, for example.
The following Modbus functions are supported:
Code Modbus function Application
1 Read Coils Read state of several digital outputs in bit format
3 Read Holding Registers Read several parameters
5 Write Single Coil Write a single digital output in bit format
6 Write Single Register Write a value into a single holding register
15 Write Multiple Coils Write several digital outputs in bit format
16 Write Multiple Registers Write a value into several holding registers
The electric actuator can issue the following Modbus error responses:
Error code Error Cause
1 Illegal function The function code is not supported.
2 Illegal data address A register address is invalid or write-protected.
3 Illegal data value A value contained in the data is not allowed or not
plausible.
4 Slave device failure An unrecoverable error occurred during an action.
6 Slave device busy The slave is busy and cannot accept the query.
Several important data points from the Modbus data point list are listed below. The entire da-
ta point list is available on request.

Table of Contents

Related product manuals