56 EB 8331-4 EN
Congurationlevel
9.7 Binary output
The binary output is a oating contact. The function and switching state of the binary input
can be congured as required.
− Inactive(c15=NONE): No function is assigned to the binary output.
− Errorindication(c15=FAIL): when an error (
icon) is registered, the error message is
issued at the binary output.
− Limitcontact(c15=LIM): the binary output is used as an electronic limit contact (see sec-
tion9.8). To congure this function, the required settings must be made in Codes c21 to
c23. The use of the binary output as an electronic limit contact is independent from the
optionally installed electronic limit contacts.
− Priorityposition(c15=PRIO): When the priority position function is active (c11 = PRIO),
this is registered at the binary output after the actuator stem stops moving.
− Adoptbinaryinput'sstate(c15=BIN): The binary output reproduces the logical state of
the binary input.
− Indicatemanualmode(c15=MAN): The binary output is active when the manual mode
(MAN) is active (Code 2) or the manual level in TROVIS-VIEW is active.
Code Description WE Adjustment range
c15 Function NONE NONE (inactive)
FAIL (error indication)
LIM (limit contact)
PRIO (priority position)
BIN (adopt binary input)
MAN (indicate manual mode)
c16 Switching state for active function NINV NINV (not inverted)
INV (inverted)
When c15 = LIM
c21 Electronic limit contact (binary output)
Message in case of event
NONE NONE (inactive)
HIGH (value above limit)
LOW (value below limit)
c22 Switching point of limit contact (binary
output)
10.0 % 0.0 to 100.0%
c23 Hysteresis of electronic limit contact
(binary output)
1.0 % 0.0 to 10.0%