82 EB 8331-4 EN
Decommissioning and disassembly
17.2 Levels and parameters
17.2.1 Operating level
Code Parameters Display/select (select ESC to cancel) Section
Start screen
0/1 Depending on application
u Read only 7
Operating level
1 Positioning value
u Read only
2 Operating mode AUTO (automatic mode)
MAN(manual mode)
8.1
3
1)
Positioning value (manual mode) 0.0 to 100.0% 8.1
4 Reading direction DISP,
DISP
8.2
5 Start initialization > INI 8.3
6 Application POSI (positioner)
PID (PID controller)
2STP (two-step mode)
3STP (three-step mode)
POSF (temperature closed-loop control
upon input signal failure)
8.4
8 Fast conguration level IN, OUT, DIR 9.13
9 Select key number > KEY 7.4
10 Activate the conguration level > CO 9.1
11 Activate the information level > INF 10.1
20 Activate the service level > SER 11.1
23 Activate the communication level > COM
Fatal error (can only be seen when error exists)
EF Final test failed ENDT 15
E00 Error: No initialization performed RUNT 15
E01 Error: Input signal failure FAIL 15
E02 Error: Blockage BLOC 15
E03 Error: Both limit switches are active SWI 15
E04 Error: Canceled while retracting stem SIN 15
E05 Error: Canceled while extending stem SOUT 15
E06 Error: Motor or potentiometer not turning MOT 15
E08 Plausibility error PLAU 9.14
E09 Bus failure BUS 15
1)
Only in manual mode (MAN)