68 EB 8331-4 EN
Service level
11.2 Starting zero calibration
Risk of injury due to the actuator stem extending or retracting.
Do not touch or block the actuator stem.
The actuator stem moves to the 0% end position. Following this, the actuator changes to
closed-loop operation and moves the actuator stem to the position dened by the input sig-
nal.
Code Description Adjustment range
d51 Start zero calibration ZER
Î Zero calibration can be canceled at all times by selecting ESC.
11.3 Starting initialization
Risk of injury due to the actuator stem extending or retracting.
Do not touch or block the actuator stem.
Î The procedure is described in section8.3 on page44.
Code Description WE Adjustment range
d52 Start initialization INI
Î Initialization can be canceled at all times by selecting ESC.
11.4 Restarting the actuator (reset)
The actuator can be restarted by performing a reset. Upon restart, the actuator goes into the
operating mode previously set unless a different restart condition has been dened (see sec-
tion9.9 on page57).
Code Description Adjustment range
d53 Perform reset RES
WARNING
!
WARNING
!