EB 8331-4 EN 95
Decommissioning and disassembly
HR Designation Access
Transmission range Indicating range
Start End Start End
Operating values (outputs)
18 Travel in % R 0 1000 0 100.0
19 Travel in mm R 0 1000 0 100
20 Set point deviation of positioner in % (positioning
value/travel)
R –1000 1000 0 100
21 Set point deviation of PID controller in % (set point/
process variable)
R –1000 1000 0 100
Operating values (position feedback)
22 Position feedback in % R 0 1000 0 100.0
23 Position feedback in mA/V R 0 240 0 24.0
24 Unit of position feedback R 0 1 0 1
Manual level of control station
25 Manual positioning value in manual level of control
station in %
R/W 0 1000 0 100.0
26 Set point deviation of manual level (control station)
in %
R –1000 1000 –100.0 100.0
Process data
27 Positioning value (manual level on site) in % R 0 1000 0 100.0
28 Status of positioning value R
Binary operating data
Class Designation COILS (1-bit) Access Status 0 Status 1
Operating states
1 Error during operation R No Yes
2 Maintenance demanded R No Yes
3 Manual level on site active R No Yes
4 Enable manual level of control station (travel adjustment) R/W *H No Yes
Binary input
5 Binary input status R Off On
6 Binary input (switching contact) R Off On
Limits
7 State of electronic limit contact 1 R Off On
8 State of electronic limit contact 2 R Off On
9 Electronic limit contacts exist R Off On