EasyManuals Logo

Samson 373 Series Operating Instructions

Samson 373 Series
132 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #28 background imageLoading...
Page #28 background image
28 EB 8389 EN
Statistical information
of the travel range and remains there for
longer than six seconds (see section5.4.1).
The PST diagnostic parameter 'Step start'
must be within the dened range of the
'Tolerance limit of step response' for the
partial stroke test to start.
After the partial stroke test is completed, the
valve moves back to its last position (fail-safe
position or operating point).
Canceling the partial stroke test (PST)
The partial stroke test is canceled whenever
the set point (
) leaves the range between
'Limit fail-safe position' and 'Limit operating
point'.
After the partial stroke test is canceled, the
valve moves back to its last position (fail-safe
position or operating point).
Dening parameters
1. Select 'Open/Close valve' as the appli-
cation type.
2. Dene parameters for on/off valve.
3. Dene parameters for partial stroke test
(PST).
1.
Start-up
Application type (Code 49 - h0): Open/
Close valve
2.
Settings > Positioner > Reference variable
Operating point (Code 49 - h1)
1)
:
0.0 to 100%, [100%]
Limit fail-safe position (Code 49 - h2)
1)
: 0.0
to 20.0 %, [12.5 %]
Limit operating point (Code 49 - h5)
1)
:
55.0 to 100.0 %, [75.0 %]
3.
Diagnosis > Tests > Partial stroke test
See section 5.4
1)
Not Type3730-5 and Type3731-5
4.1.1 On/off diagnosis
3730-2 3730-3 3731-3 3730-4 3730-5 3731-5
The diagnosis for on/off valves provides
statements on the valve end position, transit
times (rising/falling) and the breakaway
times (rising/falling). Data are constantly re-
corded in automatic mode. This monitoring
function does not need to be activated.
The positioner compares the current break-
away time, transit time and valve position
with the values recorded during the reference
measurement (rst analysis) while the plant is
running.
Dening parameters
1. Enter limits for monitoring (see sec-
tion4.1.2).
2. Select classication for status message.
1.
Diagnosis > Statistical information > Open/
Close
Limit value time analysis (Code 49 - h7):
0.6 to 30.0s, [0.6s]
Limit value travel analysis
(Code 49 - h8):
0.3 to 100.0%, [0.3%]
2.
Settings > Positioner > Error control > Classi-
cation report > Extended > Open/Close or
Settings > Positioner > Diagnosis congura-
tion > Classication
Open/Close status active (Code 49- h9):
[
], , , ( ), ( )

Table of Contents

Other manuals for Samson 373 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Samson 373 Series and is the answer not in the manual?

Samson 373 Series Specifications

General IconGeneral
BrandSamson
Model373 Series
CategoryValve Positioners
LanguageEnglish

Related product manuals