EB 8389 EN 91
Dynamic HART® variables
Table4: Dynamic HART
®
variables assignment
Variable Meaning Unit
Reference variable Reference variable %
Valve set point Valve set point %
Target position Target position %
Valve position Process variable %
Set point deviation e Set point deviation e %
Absolute total valve travel Absolute total valve travel
Binary input status 0 = Not active
1 = Active
255 = –/–
Internal solenoid valve/forced venting status 0 = De-energized
1 = Energized
2 = Not installed
Condensed state 0 = No message
1 = Maintenance required
2 = Maintenance demanded
3 = Maintenance alarm
4 = Out of specication
7 = Function check
Temperature Temperature °C
Sound pressure level (leakage detection) Sound pressure level (leakage detection) dB