7-2 EB 2512
Operation
An initial adjustment of the set point can also
be made by changing the spring tension un-
tilthedistancex(seeFig.7-1andTable7-1)
is reached.
Note that during initial set point adjustment
only a rough set point adjustment is per-
formed by turning the set point adjustment
until the distance x is reached. The special
properties of the process medium and plant
are not taken into account in this case.
Check the pressure at the pressure gauge
downstream of the regulator for a precise set
point adjustment.
X
Set point
adjuster (6)
Fig.7-1: Set point adjustment with dimension x
Note
Table7-1: Set point adjustment · Dimension
x
Set point
range
Valve size DN
8to16bar 15 to 25 32 to 50 65 to 100
Set point
10bar x=89mm
x=106mm
x=133mm
12bar x=97mm
x=117mm
x=150mm
14bar
x=104mm x=128mm
x=168mm
4.5to10bar
Set point
5.9bar x=85mm
x=100mm
x=131mm
7.3bar x=93mm
x=112mm
x=152mm
8.6bar
x=101mm x=123mm
x=172mm
2to5bar
Set point
2.8bar x=83mm x=97mm x=126mm
3.5bar x=92mm
x=110mm
x=170mm
4.3bar
x=100mm x=122mm
x=184mm
0.8to2.5bar
Set point
1.2bar x=79mm x=92mm x=117mm
1.7bar x=89mm
x=106mm
x=142mm
2.1bar x=99mm
x=121mm
x=167mm
0.2 to 1.2bar
Set point
0.45bar x=71mm x=81mm x=98mm
0.70bar x=83mm x=98mm x=127mm
1.0bar x=95mm
x=117mm
x=157mm
0.1 to0.6bar
Set point
0.23bar x=71mm x=81mm x=98mm
0.35bar x=83mm x=98mm x=127mm
0.48bar x=95mm
x=115mm
x=157mm
0.05to0.25bar
Set point
0.10bar x=70mm x=80mm x=92mm
0.15bar x=81mm x=95mm x=116mm
0.20bar x=91mm
x=110mm
x=139mm