EB 5824-2 EN 41
Conguration
9.3 Blockage
9.3.1 Blocking protection
Theblockingprotectionpreventsthevalvefromseizingup.Iftheactuatorstemisinthe
closedposition(0%),itisextendedslightlyandthenmovedbacktotheclosedposition24
hours after it last moved.
Movement of the actuator stem caused by the activated blocking protection is indicated by
the yellow LED:
2 4
6
8
10
On
Of
f
T
ime [s]
Blockingprotectionsettings: Settings\Actuator\Blockage
Function WE Adjustment range
Blockingprotection No Yes/No
9.4 Travel
9.4.1 Limited travel range
The Limited travel rangeparameterdeterminesin%howfartheactuatorstemcanmoveat
themaximum.Thetraveldeterminedduringinitializationactsasthereference.
Settings\Actuator\Travel
Function WE Adjustment range
Limited travel range 100.0% 30.0to100.0%
9.4.2 Travel adjustment
Travel adjustment can be made to be absolute or relative. The way the travel adjustment is
made affects the control behavior.