EB 5824-2 EN 43
Conguration
Stroking speed
The actuator stem moves to the position determined by the input signal at the selected strok-
ingspeed.Therearethreespeedlevels:
− Slow =0.135mm/s
− Standard =0.197mm/s
− Fast =0.365mm/s
Speedsettings:Settings\Actuator\Travel
Function WE Adjustment range
Velocity Standard Slow, Standard, Fast
The transit time is calculated from the travel and the stroking speed. The transit time is the
time that the actuator stem needs to move through the adjusted travel.
Thefollowingapplies:
Transit time in s
=
Travel in mm
Stroking speed in mm/s
Deadband(switchingrange)
The dead band determines how sensitive the actuator reacts. A change in the input signal by
thehysteresisrstcausesaminimallysmallchangeinthevalveposition.
Deadbandsettings: Settings\Actuator\Travel
Function WE Adjustment range
Dead band (switching range) 2.0% 0.5to5.0%
9.4.4 Characteristic
Thecharacteristicexpressestherelationbetweentheinputsignalandtheactuatorstemposi-
tion.
Perform the characteristic settings in the Settings folder (Actuator\Characteristic):
Note