EB 5824-2 EN 55
Malfunctions
11 Malfunctions
Î Troubleshooting(seeTable4).
Contact SAMSON's After-sales Service for malfunctions not listed in the table.
Table4: Troubleshooting
Error Possible reasons Recommended action
Actuator stem does not move. Actuator is blocked.
Î Check attachment.
Î Remove the blockage.
No or incorrect supply voltage
connected.
Î Check the supply voltage
and connections.
Actuator stem does not move
through the whole range.
No or incorrect supply voltage
connected.
Î Check the supply voltage
and connections.
The actuator does not control the
valve position.
Theactuatorwasnotinitialized
during start-up.
Î Check the switch position
of the function and direc-
tion of action switches
Î Initializetheactuator.
The mounting has been changed.
11.1 Emergency action
The valve, on which the electric actuator with fail-safe action is mounted, is moved to its fail-
safepositionuponsupplyvoltagefailure(seesection3.1).
The plant operator is responsible for emergency action to be taken in the plant.
Emergency action in the event of valve failure is described in the associated valve documen-
tation.