19
4.3.3 Audible alarm and LED indication of UPS operating status and faults
4 Operation
●:On
★:Flash
↑:Depending on other conditions
LED indicators
No. Operating status
1# 2# 3# 4# 5# 6# 7# 8# 9# 10#
Audible
alarm
1 0%--35% load ● ● ● None
2 36%--55% load ●
●
●
●
None
3 56%--75% load ●
●
●
●
●
None
4 76%--95% load ● ● ● ● ● ● None
5
Normal
mode
96%--105% load
●
●
●
●
●
●
●
None
6
0%--25% battery
capacity
●
● ●
Once every 1
second
7
26%--50% battery
capacity
●
●
●
●
Once every 4
seconds
8
51%--75% battery
capacity
●
●
●
●
●
Once every 4
seconds
9
76%--100% battery
capacity
●
●
●
●
●
●
Once every 4
seconds
10
Battery
mode
100% battery
capacity
●
●
●
●
●
●
●
Once every 4
seconds
11 Bypass mode
↑
↑
↑
↑
●
●
●
Once every 2
minutes
12
Overloaded in Normal mode,
switch to Bypass mode
●
●
●
●
●
●
●
●
Continually
ring
13 Utility power fault
↑
↑
↑
↑
●
↑
★
↑
↑
↑
14
Overload in Battery mode,
pre-alarm
●
●
●
●
Twice every 1
second
15
Overloaded in Battery mode,
output off
●
●
Continually
ring
16 Overheating fault
●
●
↑
↑
Continually
ring
17 Inverter fault
●
●
↑
↑
Continually
ring
18 BUS voltage fault
●
●
↑
↑
Continually
ring
19
Utility power input NTC open
circuit
●
●
●
Continually
ring
20 Over voltage of charger output
●
●
↑
↑
Continually
ring
21 Battery fault
↑
↑
↑
↑
↑
●
★
↑
22
Reversed polarity (L,N)
of input
wiring
or disconnected with
ground.
↑
↑
↑
↑
●
↑
★
↑
↑
Once every 2
minutes
23 Charger or battery fault
●
★
Once every 1
second
24 Output short circuit
●
●
●
↑
Continually
ring
25 Fan failure ●
●
● ↑
↑
↑
Once every 1
second
↑
↑