4.3.3 Audible alarm and LED indication of UPS operating status and faults
4 Operation
●:On
★:Flash
↑:Depending on other conditions
LED indicators
No. Operating status
1# 2# 3# 4# 5# 6# 7# 8# 9# 10#
Audible
alarm
1 0%--35% load None
2 36%--55% load
None
3 56%--75% load
None
4 76%--95% load None
5
Normal
mode
96%--105% load
None
6
0%--25% battery
capacity
Once every 1
second
7
26%--50% battery
capacity
Once every 4
seconds
8
51%--75% battery
capacity
Once every 4
seconds
9
76%--100% battery
capacity
Once every 4
seconds
10
Battery
mode
100% battery
capacity
Once every 4
seconds
11 Bypass mode
Once every 2
minutes
12
Overloaded in Normal mode,
switch to Bypass mode
Continually
ring
13 Utility power fault
14
Overload in Battery mode,
pre-alarm
Twice every 1
second
15
Overloaded in Battery mode,
output off
Continually
ring
16 Overheating fault
Continually
ring
17 Inverter fault
Continually
ring
18 BUS voltage fault
Continually
ring
19
Utility power input NTC open
circuit
Continually
ring
20 Over voltage of charger output
Continually
ring
21 Battery fault
22
Reversed polarity (L,N)
of input
wiring
or disconnected with
ground.
Once every 2
minutes
23 Charger or battery fault
Once every 1
second
24 Output short circuit
Continually
ring
25 Fan failure
Once every 1
second