24
7 Specifications
Electrical
17.
Model
C1K C1KS C2K C2KS C3K C3KS
Rating 1kVA/800W 2kVA/1600W 3kVA/2400W
Input system Single phase & earth ground
Rated voltage 220VAC
Voltage range
115VAC300VAC
Frequency 50Hz
Power factor 0.98
Input
Voltage range of
bypass
80VAC×(1±5%) 285VAC×(1±5%)
Output system Single phase & earth ground
Rated voltage 220VAC
Power factor 0.8
Voltage precision ±2%
Normal
mode
1.The output frequency synchronizes with the input
frequency when the input frequency is in the range
of 46 Hz
54 Hz
2.The output frequency is 50Hz when the input
frequency is not in the range of 46 Hz54 Hz
Output
frequency
Battery
mode
50
0.2 Hz
Inverter overload
capacity
Utility
power
25?
108%±5%<Load?150%±5% 25s transfer to bypass
150%±5%< Load <200%±5% 300ms transfer to
bypass
0ms Normal mode?Battery mode
Transfer time
<4ms
Normal mode?Bypass mode
Output
Crest factor 3:1 (max)
Batteries voltage 36VDC 72VDC 96VDC
Battery capacity
×
Quantity
12VDC
×
3 12VDC
×
6 12VDC
×
8
Backup Time
25?
Full load ?5min (Standard)
Battery
Battery charge time
Charger to 90% battery capacity in 5 hours
Standard
Dependent on the capacity of external batteriesLong
backup time
PDF created with pdfFactory Pro trial version www.pdffactory.com
±