24
7 Specifications
Electrical
17.
Model
C1K C1KS C2K C2KS C3K C3KS
Rating 1kVA/800W 2kVA/1600W 3kVA/2400W
Input system Single phase & earth ground
Rated voltage 220VAC
Voltage range
115VAC~300VAC
Frequency 50Hz
Power factor 0.98
Input
Voltage range of
bypass
80VAC×(1±5%) ~285VAC×(1±5%)
Output system Single phase & earth ground
Rated voltage 220VAC
Power factor 0.8
Voltage precision ±2%
Normal
mode
1.The output frequency synchronizes with the input
frequency when the input frequency is in the range
of 46 Hz
~
54 Hz
2.The output frequency is 50Hz when the input
frequency is not in the range of 46 Hz~54 Hz
Output
frequency
Battery
mode
50
0.2 Hz
Inverter overload
capacity
(
Utility
power
,
25?
)
108%±5%<Load?150%±5% 25s transfer to bypass
150%±5%< Load <200%±5% 300ms transfer to
bypass
0ms (Normal mode?Battery mode)
Transfer time
<4ms
(
Normal mode?Bypass mode
)
Output
Crest factor 3:1 (max)
Batteries voltage 36VDC 72VDC 96VDC
Battery capacity
×
Quantity
12VDC
×
3 12VDC
×
6 12VDC
×
8
Backup Time
(
25?
)
Full load ?5min (Standard)
Battery
Battery charge time
Charger to 90% battery capacity in 5 hours
(
Standard
)
Dependent on the capacity of external batteries(Long
backup time
)
℃
℃
≥
≤
PDF created with pdfFactory Pro trial version www.pdffactory.com
±