25
7 Specifications
Environmental
37.
47. EMC
Item Standard Level
ESD
IEC61000-4-2 LEVEL4
RS IEC61000-4-3 LEVEL3
EFT IEC61000-4-4 LEVEL4
Surge IEC61000-4-5 LEVEL4
57. Safety
Comply with GB4943-2001,IEC62040-1 and CE requirements.
67. Industry Standard
Comply with EN62040YD/T 1095-2000 requirements.
Mechanical
27.
Model W*H*D(mm) Weight(kg)
C1K
145
×
220
×
355
12 kg
C1KS
145×220×355
6.5 kg
C2K
190×318×383
23 kg
C2KS
190
×
318
×
383
10.5 kg
C3K
190
×
318
×
433
28 kg
C3KS
190
×
318
×
433
11.5 kg
Item Normal range
Ambient temperature
0? 40?
Environment humidity 20
%
90%
No condensation
Altitude
Lower than 1000m: no derating
Over 1000m :1% derating for every 100m rise
Storage temperature
-15? 45?
PDF created with pdfFactory Pro trial version www.pdffactory.com