SINUS MINI High performance Vector Control Inverter User Manual
26
F0.04
Main frequency
setting gain K1
0.000-9.999
1.000
+
F0.05
Zero frequency
source of
multi-speed mode
0 Reserved
1 Digital frequency of F0.11
2External analog signal:AI1
3External analog signal:AI2
4Communication given
0
+
F0.06
Auxiliary frequency
setting option
0External analog signal AI1(0~10V)
1External analog signal AI2(0~20mA)
2External analog signal AI1(0~10V)+/- polarity
3External analog signal AI2(0~20mA)+/- polarity
4PID
5 Keyboard Increase and decrease key
0
+
F0.07
Auxiliary frequency
range selection
0Relative maximum frequency
1Relative primary given
0
+
F0.08
Auxiliary frequency
setting range
0-100%
100
+
F0.09
Setting Frequency
selection
0Main frequency
1Auxiliary frequency
2Main frequency + Auxiliary frequency
3Main frequency - Auxiliary frequency
4switch between Main frequency and Auxiliary
frequency
5switch between Main frequency and Main
frequency + Auxiliary frequency
6switch between Main frequency and Main
frequency - Auxiliary frequency
7MAXMain frequencyAuxiliary frequency
8MINMain frequencyAuxiliary frequency
9Traverse operation
0
+
F0.10
UP/DOWN setting
store selection
0Store
1Not Store
0
#
F0.11
Digital frequency
setting
0~600.0Hz
50.00
#