7-1-2. Outdoor Unit
AVOID:
heat sources, exhaust fans, etc. (Fig. 4)
damp, humid or uneven locations.
DO:
choose a place as cool as possible.
choose a place that is well ventilated.
allow enough room around the unit for air intake/
exhaust and possible maintenance. (Fig. 5a)
provide a solid base (level concrete pad, concrete
block, 10
×
40 cm beams or equal), a minimum of
10 cm above ground level to reduce humidity and
protect the unit against possible water damage
and decreased service life. (Fig. 5a)
Install cushion rubber under unit’s feet to reduce
vibration and noise. (Fig. 5b)
use lug bolts or equal to bolt down unit, reducing
vibration and noise.
Outdoor unit
Hot air
Heat source
Exhaust fan
NO
Fig. 4
Air intake
Concrete
or equal
About 10 cm
Min. 10 cm
Anchor bolts
(4 pcs.)
About 40 cm
Fig. 5a
Cushion rubber
Fig. 5b
Air intake Min. 10 cm
Air discharge
Min.
5 cm
Min.
40 cm
Valve
side
Min.
25 cm
Min.
2 m
Min.
2 m
Min. 10 cm
Air intake
Ground
Obstacle
Obstacle above
Air discharge