9-2-7. Sensing of Frosting and Release of Defrosting
●
Non-stop defrosting
If the air conditioner is turned off during the defrosting cycle, it will continue defrosting and turn
itself off after defrosting is completed.
9-2-8. CT (Peak current cut-off control)
●
This function prevents the circuit breaker or fuse from operating to open the circuit. This function works when
electrical current has increased due to an increase in the cooling / heating load, or to a decrease in the power
supply voltage. In these cases, operation frequency is reduced or operation is interrupted automatically to con-
trol the electrical current for operation.
●
When the cause of the increase in electrical current is rectified, the system will resume operation in the original
mode.
Operation at 230V
Electrical current setting for Cooling operation is used during Defrosting operation.
Heating operation
Frost sensing
Non-stop defrosting
Defrosting Sequence
Releasing of defrosting
Outdoor heat exchanger temp.
Ambient temp.
Frosting
area
0
●
●
Outdoor fan ON
4-way valve Heating mode
● Frosting is assumed according to the outdoor
temp., outdoor
heat exchanger
temp.,and
operation time.
●
●
●
Outdoor heating exchanger temp. is over 14°C.
Defrosting operation lasts 12 minutes (maximum).
2 minutes after it is stopped, compressor is ON.
4-way valve is Heating mode. Outdoor fan is ON.
EM Valve ➞
OFF
●
●
●
●
Compressor ➞
ON
Outdoor fan ➞
OFF
Indoor fan ➞
OFF
4-way valve ➞
Heating mode
● EM Valve ➞
ON●