EasyManuals Logo

Satec PM130 PLUS User Manual

Satec PM130 PLUS
161 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #160 background imageLoading...
Page #160 background image
Appendix G Device Diagnostic C O D E S
160 PM130 PLUS Powermeter Series
Appendix G Device Diagnostic Codes
Table 40: Device Diagnostic Codes
Diagnostic
Code
Diagnostic
Message
Description
Reason
2
dAtA
Memory/Data fault
Hardware failure
3
rSt
Hardware watchdog reset
Hardware failure
5
CPU
CPU exception
Hardware failure
6
runt
Run-time software error
Hardware failure
7
tout
Software watchdog
timeout
Hardware failure
8
PWr.UP
Power Down/Up
Normal power-up sequence
9
rStrt
Warm restart
External restart via
communications or by
firmware upgrade
10
ConF
Configuration reset
Corrupted setup data has
been replaced with the
default configuration
11
rtc
RTC fault
The clock time has been lost
13
Lo.bAt
Low battery (with a
battery backup unit)
Battery replacement is
required
15
EEPr
EEPROM fault
Hardware failure
See Diagnostics Display in Chapter 3 for more information on the PM130
PLUS built-in diagnostics.

Table of Contents

Other manuals for Satec PM130 PLUS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Satec PM130 PLUS and is the answer not in the manual?

Satec PM130 PLUS Specifications

General IconGeneral
BrandSatec
ModelPM130 PLUS
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals