SATEL MICRA 3
1. MODULE FEATURES
• 4 individually programmable hardwired zones with optional operation in digital (NO, NC,
EOL) or analog mode.
• Additional TMP hardwired zone to supervise NO or NC wiring type:
– acting as a tamper loop input in communication device mode,
– programmable in alarm device mode.
• 2 programmable NO or NC type relay outputs.
• OC type output serving as indicator of GSM network logging problems, or as armed mode
indicator.
• High-current (0.5 A) output, with polymer fuse, to perform the function of power supply
output (optionally, it can perform the power input function).
• Ability to remotely control the relay outputs with the CLIP service.
• Built-in radio waves superheterodyne receiver:
– support for up to eight 433 MHz keyfobs manufactured by SATEL;
– support for up to eight 433 MHz wireless detectors manufactured by SATEL;
– support for MKP-300 wireless keypad.
• Non-volatile 1024 event log buffer.
• Information on the status of supervised equipment and module through reporting in
Contact ID format (GPRS, SMS) or messaging (SMS, CLIP).
• Encrypted transmission of events sent with the use of GPRS technology.
• Capability to automatically replace the GPRS transmission with SMS message, if there are
problems with GPRS transmission.
• Periodical test transmissions for checking availability of the module:
– to selected telephone numbers (with the use of SMS message or CLIP service);
– to monitoring stations.
• Capability of generating additional test transmissions:
– after identification of the calling party's telephone number (CLIP service);
– after receiving command from the GPRS-S
OFT program.
• Capability of arming / disarming the premises by means of CLIP service.
• Option to check the status of available resources and account validity of the SIM card
installed in the module.
• Listen-in feature for alarm verification by means of a telephone (external microphone
required).
• Module configuration:
– locally – through the RS-232 (TTL) port;
– remotely – through the GSM network (GPRS technology)
– remotely – using SMS messages.
• Indicator of GSM signal level received by industrial cellular telephone and an indicator of
troubles connected with logging into the GSM network.
• Automatic module restart capability.
• Switching mode power supply, output current 2 A with short-circuit protection, provided
with battery status monitoring and low battery disconnection circuit.
• Power supply with 18 V AC (±10%).
• Possibility to power with 12 V DC.