SATEL MICRA 29
I – AC voltage loss.
– AK – information on the battery status:
i – battery full,
I – battery low.
– OUT 1 ÷ OUT2 – information on relay outputs status OUT 1 ÷ OUT2:
o – output inactive,
O – output active.
– EVb – the maximum number of transmissions has been reached (see: "Limit number of
notifications to" parameter, "GSM telephone, Monitoring stations" tab).
Reaction to CLIP / Listen-in initiation only when number is on list of telephones for
messaging – if this option is enabled, the module will only send test transmission or SMS
message with status information, or will initiate listen-in, when the telephone number,
identified owing to the CLIP service, is one of the numbers programmed in the “GSM
telephone, Monitoring stations" tab on the “Telephone numbers for messaging and test
transmissions" list.
Note: If the “Reaction to CLIP / Listen-in initiation only when number is on list of telephones
for messaging" option is not enabled, the test transmissions and SMS messages with
information on device status:
– for the numbers in the list, they will be sent by the module immediately,
– for the numbers not in the list, they can be sent by the module every 10 minutes at
the most.
Listen-in
Rings to answer – enter in this field the number of rings after which the module will answer
the call and turn on the microphone. You can program values from 0 to 9. If value 0 is
programmed, the listen-in feature is disabled.
Micr. Sens. – microphone sensitivity can be programmed within the range from 0 to 15.
4.3.5 „CLIP / SMS MESSAGING” TAB
Notification can be effected by means of SMS messages or by using the CLIP service (when
the CLIP service is used, the module does not inform about zone restore / end of trouble).
Note: For the analog zones, the messaging parameters are to be defined separately for each
of the defined thresholds.
CLIP T1 – T4 – select the fields of telephones (see: numbers in the list "Telephone numbers
for messaging and test transmissions", programmed in the "GSM telephone, Monitoring
stations" tab), which will be informed about a change in the given zone status or
occurrence of the particular trouble by using the CLIP service.
SMS T1 – T4 – select the fields of telephones (see: numbers in the list "Telephone numbers
for messaging and test transmissions", preprogrammed in the "GSM telephone, Monitoring
stations" tab), to which an SMS message is to be sent to notify about a change in the
given zone status or occurrence of the particular trouble.
Violation/pass – content of the SMS message that will be sent on the zone violation /
exceeding the preprogrammed zone voltage value (rise above the defined value at
threshold H or drop below the defined value at threshold L) / occurrence of trouble. The
message may consist of up to 24 characters. If the field is left blank, the message will not
be sent.
Restore – content of the SMS message that will be sent on the zone restore / end of trouble.
The message may consist of up to 24 characters. If the field is left blank, the message will
not be sent.